Question 1
A service handbook specifies a 30-second wait followed by voltage verification after all supplies are isolated. To support that wait, a 400 V DC link must decay to 60 V or less within 30 seconds. Its capacitor is 220 microfarads ±20%, and the bleeder resistor is ±5%. Use V(t) = 400 exp[-t/(RC)], with R in ohms and C in farads; neglect other leakage. All candidates have adequate voltage and power ratings. To minimize continuous bleeder loss, select the largest listed nominal resistance that meets the discharge requirement at the worst-case tolerances.
Show answer & explanation
Correct answer: B - 47 kilohms